Detail |
This device is designed to interface and convert RTD100, linear resistor, thermocouples or potentiometer signals coming from the hazardous to the safe area. |
Input: |
» BER: RTD100 with fixed scale to be defined according codification |
|
» BEC: Thermocouple with fixed scale and type to be defined according codification |
|
» BEP: Potentiometer from 0-1kOhm to 0–50kOhm |
Output: |
Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request |
Supply: |
24 VDC |
Model: |
1 channel |
Setting: |
Adjustment potentiometer for the source and the curve on the front |
green LED |
for presence of voltage |
Installation : |
Safe area |
Options: |
» Screw terminals |
EC Type examination certificate number : |
LCIE 02 ATEX 6104X |
IECEx conformity certificate : |
LCI 09.0013X |
ATEX/IECEx classification : |
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD] |